Ingress And ADC Reconstruction
Note
Insert the user-provided I/O diagram here after the Visio source and image are available.
System Role
UUID: 7F8AC58C-1708-486C-AF4F-2D690F3CE607
Summary: The Host PC ingress-and-ADC-reconstruction system qualifies received transport candidates as complete measurement frames and preserves ordered raw ADC counts with frame identity, status, and the documented 3648 effective detector pixels for downstream processing.
System Objectives
UUID: 8A67F948-8087-42D0-A37D-1AA34DB6D15B
Objective 1: Traffic collection. Ingress and ADC Reconstruction shall collect measurement traffic only while the acquisition interface is available and shall keep non-measurement traffic out of the processing pipeline.
Rationale: Separating measurement and non-measurement traffic prevents status text or unsupported content from becoming detector data.
Objective 2: Frame validation. Ingress and ADC Reconstruction shall verify frame identity, status, completeness, and the presence of all 3648 effective samples before releasing a frame.
Rationale: These checks prevent partial or structurally incorrect frames from being interpreted as complete measurements.
Objective 3: Output and rejection. Ingress and ADC Reconstruction shall preserve accepted raw samples in acquisition order and shall report incomplete frames, malformed content, unsupported content, and frame-identity gaps.
Rationale: Explicit rejection evidence supports recovery without inventing samples or redefining the Integration-owned wire format.
Documentation Relationship
UUID: 703CB7D9-EDC2-4560-8A11-4C321FC92D56
Documentation |
Responsibility |
|---|---|
Accepted inputs, produced outputs, metadata, and unavailable or incompatible conditions. |
|
Ordered behavior, decisions, and processing conditions. |
|
Observable failure or qualification conditions and operator gating. |
|
Behavior-local scenarios and the current acceptance basis. |
|
Supported calculation or explicit absence of one, plus open requirements. |
|
Behavior claim, local traceability state, open decisions, and evidence method. |
Integration Boundary
UUID: 24659D9A-0778-4E53-9580-C80921452D60
Summary: The Host PC ingress-and-ADC-reconstruction system receives a
transport candidate from the Integration boundary and determines whether it is
eligible to become a complete measurement frame. Framing, chunking, encoding,
resynchronization, recovery, and total transported geometry beyond the 3648
effective detector pixels are Not In Docs for this system and remain owned
by Integration.